Conductivity and TDS may appear on the same controller, but they are not independent measurements. The conductivity cell measures an electrical property; a controller may calculate TDS using a configured relationship. Choose the value that matches the operating decision and specification.
Decision table
| Value | Use it when | Main limitation |
|---|---|---|
| Conductivity | Direct online trend of ionic changes, RO performance or rinse progress | It does not identify individual ions or a specific contaminant |
| Resistivity | Very low-conductivity water is easier to interpret on an inverse scale | Sensor range and temperature basis still require confirmation |
| Calculated TDS | The project requires ppm or mg/L with an agreed conversion basis | The conductivity-to-TDS factor is not universal |
Choose conductivity for process trending
Conductivity is useful for comparing RO feed and permeate, monitoring rinse water and identifying a shift from an established baseline. Temperature affects conductivity, so use a documented compensation arrangement and compare values on the same basis. Conductivity does not prove microbiological, organic or ion-specific water quality.
Use TDS only with a defined conversion basis
A simplified relationship is calculated TDS = conductivity × configured factor. The factor depends on water composition, units and method. Record the factor and compare it with representative reference results before relying on the display.
Controller and sensor comparison
| Model | Measurement direction | Integration direction |
|---|---|---|
| EC-703 | Conductivity, TDS and resistivity | Isolated 4–20mA output and two relay outputs |
| EC-702 | Conductivity, resistivity, salinity and TDS | Two isolated 4–20mA outputs and RS485 Modbus RTU |
| ECS-7301 | Conductivity, resistivity, salinity and TDS | Two isolated 4–20mA outputs, RS485 Modbus RTU, relays and logging |
Confirm cell constant, liquid, range, temperature, pressure, wetted materials, installation and signal mapping. See the RO conductivity monitoring guide for membrane systems.
Commissioning checklist
- Define the operating decision and display unit.
- Match the cell constant to actual minimum and maximum conductivity.
- Configure temperature compensation.
- Record the TDS factor if displayed or transmitted.
- Scale the 4–20mA output or digital register.
- Compare with a suitable reference at the operating range.
Common mistakes
- Reporting TDS without recording its conversion factor.
- Comparing different temperature-compensation settings.
- Using one cell across low-purity and high-salt ranges without confirmation.
- Assuming the same conductivity means the same chemistry.
Questions for the specification
State the unit, reference temperature, compensation method, normal and maximum range, reference procedure and transmitted value. If the operator sees TDS while the PLC receives conductivity, document both mappings.
Request a configuration review
Send your liquid, range and reporting requirement for model selection